The Virginia Tech Calibration System, © 2011, Javier Fernandez
5. DYNAMIC TESTING
This chapter shows the results of test performed by the Virginia Tech Calibration System
and explain the interaction between the hardware and the software used to assess the dynamic
performance of a PMU, DUT A.
5.1. Step Change response
This section shows the tests performed for determining performance of PMUs in response
to step changes. The step change response tests include magnitude, phase angle, and frequency
tests.
The Run_Step_Test_on_DUTs_add VI is used to run the step change response tests. It
uses the concept of interleaving phasors developed in [15]. Each test is executed using the
NI_DUT_Step_add VI. The error data is sent to the Display&Store VI. This program displays
the errors and saves the data to NI DIAdem files.
The NI_DUT_Step_add VI Block diagram is shown in Figure 5.1. The Run_NI_Add VI
generates the test signals and starts the NI PMU. The Collect_data VI gathers and aligns the
phasor data according to their time stamps. The Analyze_Data VI performs the phasor
comparisons.
The Run_DUT_TCP_add VI is executed simultaneously with the
Run_Step_Test_on_DUTs_add VI to start the DUT.
The test parameters are inputted in the Run_Step_Test_on_DUTs_add VI Front Panel,
shown in Figure 5.2.